Honeywell EN2H-0221GE51 R0808 Heating System User Manual


 
SDC / DHC Hydraulic Components
EN2H-0221GE51 R0808 151
The boiler parallel shift of the tank loading pump (parameter) acts
on the mixed heating circuit demand.
The boiler parallel shift of mixed heating circuits acts on the heat
generator, provided the tank loading pump control mode has not
been set to "external storage tank".
The optional return flow limit acts on the flow mixture according to
the setting.
The hot-water pre-control acts only on hot-water loading
configured in the same device.
7.2.6 Mode of operation: Hot-water pre-control
When operating in combination with hot-water pre-control,
parameter 08 (tank drainage protection) does not act directly on
the heat generator, but on the hot-water pre-control.
Parameter 08 is always adjustable for function with pre-mixer.
Here, the "OFF" and "ON" settings have different effects, which
are described in the following.
With the setting "OFF", there will be no start-up protection through
the hot-water pre-control. The tank loading pump is switched on
without any delay.
With the setting "ON", the tank loading pump is switched on only
when the flow sensor detects that the hot-water setpoint
temperature + ½ switching difference hot water (without offset) is
reached:
)(09 HWPWHHWPC
tsetpointsetpoin
+
=
SLP = ON if
HWtsetpoinactual
SDHWHWPC
2
1
+
SLP = OFF if
tsetpoinactual
HWHWPC
Function