5.4.9 "Solar" menu (SOLAR)
The parameters in this menu refer to special settings with regard
to the solar applications.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.
Para-
meter
Designation Setting range / Setting values Factory
setting
Setting
01 Switch-on
differential
(Setting value of parameter
02 + 3 K) to 30 K
10
02 Switch-off
differential
2 K to (setting value of parameter
01 – 3 K)
5
03 Minimum runtime
of solar charging
pump
0 ... 60 min 3
04 Collector maxi-
mum temperature
OFF, 70 to 210°C 210
05 Buffer maximum
temperature limit
20 ... 110°C 75
1 Priority operation
2 Parallel operation
3 Priority operation of hot-
water circuit
06 Operating mode
4 Priority operation of
buffer
07 Heat generator
cycle inhibitor
(only if parameter
06 = 1)
OFF, 0.5 to 24 h OFF
08 Solar priority
parallel switchover
OFF, 1 to 30 K OFF
OFF No heat balancing
1 Heat balancing via flow-
through calculation
09 Heat balance
2 Heat balancing via pulse
input
OFF