Honeywell EN2H-0221GE51 R0808 Heating System User Manual


 
SDC / DHC Operation
EN2H-0221GE51 R0808 109
Para-
meter
Designation Setting range / Setting values Factory
setting
Setting
1 Heating circuit
charge regulation
and hot-water circuit
1
2 Heating circuit
charge regulation
without hot-water
circuit
3 Heating circuit and
hot-water circuit
discharge regulation
4 Heating circuit
discharge regulation
without hot-water
circuit
Buffer operating
mode
5 Charge regulation
with hot-water circuit
switchover
10
6 Discharge regulation
for heat generator
11 Follow-up time of
buffer charging
pump
0 ... 60 min 3
5.4.12 "Total flow regulation" menu (MAIN SUPPLY)
The parameters in this module refer to special settings with regard
to total flow regulation.
This selection is only available if a total flow sensor is configured
on one of the variable inputs (see the "Hydraulics" menu,
parameters 08, 09 or 10).
Para-
meter
Designation Setting range / Setting values Factory
setting
Setting
01 Regulation 0 ... 50 %/K 5
03 Regulation 1 ... 600 s 180