Honeywell EN2H-0221GE51 R0808 Heating System User Manual


 
SDC / DHC Operation
EN2H-0221GE51 R0808 101
Para-
meter
Designation Setting range / Setting values Factory
setting
Setting
13 Lead time of boiler
circuit pump or
parallel heat
generator enable
(only with
appropriate
configuration in the
"Hydraulics"
menu)
0 ... 10 min 0
14 Follow-up time of
boiler circuit pump
(only with
appropriate
configuration in the
"Hydraulics"
menu)
0 ... 60 min 2
15 Follow-up time of
feeder pump (only
with appropriate
configuration in the
"Hydraulics"
menu)
0 ... 60 min 2
OFF Display of exhaust gas
temperature only
OFF
0 ... 60
min
Heat generator lock if
limit value is exceeded
for set time
16 Exhaust gas
temperature
monitoring (only
with appropriate
configuration in the
"Hydraulics"
menu)
SLT Heat generator lock if
limit value is exceeded
17 Exhaust gas limit
value (only with
appropriate
configuration in the
"Hydraulics"
menu)
50 ... 500°C 200