6.8.4 Outside temperature disable
The purpose of outside temperature disable is to prevent the heat
generator from starting up above a defined outside temperature.
If several heat generators are controlled though one device
(automatic stoker, 2-stage), all stages of the device will be
disabled with outside temperature disable.
In the case of cascaded systems with multiple devices, the entry
of an outside temperature disable is possible for each central
device so that individual levels can be blocked by the outside
temperature disable.
6.8.5 Climate zone
The climate zone is the coldest outside temperature value to be
expected.
For the heat demand coverage, this value is taken as the basis for
the design of the heating system.
This parameter defines the corresponding slope value of the
heating curve of the heating circuit with regard to the climate
zone.
5.2.3 "System Parameters" menu, Pg. 72
6.8.6 Design temperature
Until now, configuration of the heating curve calculation occurred
via the values
• Climate zone (T
ANorm
)
• Slope (S)
• Heating system (m value)
Supplemental to the slope, the setting of the design temperature
T
VLNorm
is also possible directly at the controller.
Setting range DESIGN TEMP: Setting range HC
min
to HC
max
(°C)
There is a direct relation between the HEATING CURVE and
DESIGN TEMP parameters in the following connection:
CSTCT
ANormVLNorm
°
+
−
°= 20*)20(
This means that the value of the respective other parameter
changes accordingly.