Honeywell EN2H-0221GE51 R0808 Heating System User Manual


 
SDC / DHC Hydraulic Components
EN2H-0221GE51 R0808 187
7.3.5 Hot-water production
7.3.5.1 Hot-water tank loading (SLP)
The output controls a hot-water circuit loading pump during the
respective operational-readiness times upon demand.
The hot-water daytime temperature provides for the desired hot
water temperature during hot-water circuit operational-readiness
times in automatic mode and in the PARTY and HEATING control
modes.
This set value is the initial value for the temperature specifications
that can be set for each heating cycle in the switching-time
programs. The temperature settings in the switching time
programs are automatically adjusted when the hot-water daytime
temperature is changed.
Example: Before
Daytime hot-water temperature value: 50°C
Temperatures in switching-time program:
05:00 hours – 08:00 hours 60°C
08:00 hours – 16:00 hours 50°C
16:00 hours – 22:00 hours 60°C
Example: After
Daytime hot-water temperature value: 52 °C
Temperatures in switching-time program:
05:00 hours – 08:00 hours 62°C
08:00 hours – 16:00 hours 52°C
16:00 hours – 22:00 hours 62°C
Changed settings are stored when key § or î is briefly pressed
again or after automatic return at a preset time. Once the settings
are stored, the unit automatically switches to the basic display.
5.1.2.4 "Daytime hot-water temperature" button, pg. 25
Function
Hot-water circuit -
daytime
See also