Honeywell EN2H-0221GE51 R0808 Heating System User Manual


 
Operation SDC / DHC
96 EN2H-0221GE51 R0808
Para-
meter
Designation Setting range / Setting values Factory
setting
Setting
03 OFF Display of heat
generator temperature,
room sensor off,
operation active
OFF
1 Display of room
temperature, room
sensor active, operation
active
2 Display of room
temperature, room
sensor active, operation
disabled
Room connection
(in conjunction
with room sensor)
3 Display of room
temperature, room
sensor off, operation
active
OFF
10 ...
500 %
Influence active
04 Room factor
RC Room controller active
OFF
07 Heating limit OFF, 0.5 to 40 K OFF
08 Room frost-
protection limit
5 ... 30 °C
10
09 Room thermostat
function
OFF, 0.5 to 5 K OFF
0 Regulation to average
value (outside sensor 1
+ outside sensor 2)
0
1 Regulation to outside
sensor 1
10 Assignment of
outside sensor
2 Regulation to outside
sensor 2