Honeywell EN2H-0221GE51 R0808 Heating System User Manual


 
SDC / DHC Operation
EN2H-0221GE51 R0808 107
Para-
meter
Designation Setting range / Setting values Factory
setting
Setting
10 Reset heat
balance
SET by pressing the input button
11 Volume flow 0 ... 30 L/min or L/pulse 0
12 Density of medium 0.8 ... 1.2 kg/L 1.05
13 Heat capacity of
medium
2 ... 5 KJ/kgK 3.6
14 Final switch-off
temperature
OFF, 90 to 210 °C 210
15 Test cycle of solar
charging
switchover
1 ... 60 min 10
16 Switchover tem-
perature
20 ... 110 °C 75
5.4.10 "Solid" menu (SOLID FUEL)
The parameters in this menu refer to special settings with regard
to solids regulation.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.
Para-
meter
Designation Setting range / Setting values Factory
setting
Setting
01 Minimum
temperature
20 ... 80 °C 60
02 Maximum
temperature
30 ... 100 °C 90
03 Switch-on
differential
(Setting value of parameter
04 + 3 K) to 20 K
10
04 Switch-off
differential
2 K to (setting value of parameter
03 – 3 K)
5
05 Heat generator
cycle inhibitor
OFF, 2 to 180 min OFF