Fluke 5020A Thermostat User Manual


 
Digital Communications Interface
Commands 6
6-13
<hour> indicates a one or two digit number for the hour (0 to 23) is required.
<minute> indicates a one or two digit number for the minute is required.
<second> indicates a one or two digit number for the second is required.
<baud> indicates a valid baud rate setting is required.
For query commands, specifying the MIN, MAX, or DEF parameter causes the
instrument to respond with the minimum, maximum, or default setting
respectively.
For set commands, specifying the MIN, MAX, or DEF parameters causes the
instrument to use the minimum, maximum, or default setting respectively.
Unrecognized commands or commands with incorrect syntax or invalid
parameters generate error messages that are placed in the error queue (see
SYST:ERR?).
Alarm Commands
ALARm:BATTery?
Indicates whether a battery alarm event has occurred.
Example: ALAR:BATT?
Response: 1
A value of 1 is returned if a battery alarm event has occurred. A value of 0 is returned if a
battery alarm event has not occurred.
ALARm:BATTery:ENABle?
Returns the state of the battery alarm enable.
Example: ALAR:BATT:ENAB?
Response: 0
A value of 1 is returned if the battery alarm is enabled. A value of 0 is returned if the
battery alarm is disabled.
ALARm:BATTery:ENABle <bool>
Sets the state of the battery alarm enable.
Example: ALAR:BATT:ENAB 1
The <bool> parameter turns the battery alarm enable on (1 or ON) or off (0 or OFF). This
command may be password protected (see Password Commands).
ALARm:BEEP?
Returns the state of the audible alarm enable.
Example: ALAR:BEEP?
Response: 0
A value of 1 is returned if the alarm beep is enabled. A value of 0 is returned if the alarm
beep is disabled.