Table 11 — Thermistor Resistance vs Temperature
Values for Supply-Air Temperature Sensor
(10 Kilo- ohm)
SMOKE DETECTOR/FIRE ALARM SHUTDOWN
(FSD) — To allow a smoke detector to shut the 50BV down,
remove the jumper from FSD to C and wire these terminals to a
set of normally closed contacts on the smoke detector.
ALARM (ALARM) AND WARNING (WARN) OUT-
PUTS — Two dry contacts output a discrete signal when the
alarm and warning lights on the display are lit. To pick up the
alarm output signal, wire between the ALARM and ALM-CM
terminals. To pick up the warning output signal, wire between
the WARN and ALM-CM terminals.
REMOTE OCCUPANCY (ROCC) — The 50BV unit may
be commanded by another control system or a twist timer to
become occupied and run when a set of dry contacts close. In
order for this to occur, wire the contacts to ROCC and C and
set the Local/Off/Remote switch to REMOTE.
RETURN AIR TEMPERATURE SENSOR (RAS) — The
return/mixed air temperature sensor is a 5 kiloohm temperature
sensor used as the space control point. For every degree that
the RAS is below the set point, the supply air set point will be
reset by the configured value in the custom configured RESET
RATIO. Refer to Table 12 and Fig. 31.
Table 12 — Thermistor Resistance vs Temperature
Values for Return-Air Temperature
Sensor (5 kiloohm)
Wire the sensor to PCB1 connector J3, terminals 15 and 16.
Change custom configuration as instructed in Configure the
Custom Programming Selections section. Changing this con-
figuration to YES changes the EWT input to be used as return
air temperature input.
START-UP
General —
Complete the Start-Up Checklist on page CL-1
before attempting system start-up.
CRANKCASE HEATERS — The 50BVT,U,V,W,X034-064
units include crankcase heaters. Crankcase heaters are ener-
gized as long as there is power to the unit and the compressor
is not operating.
Wait 24 hours before starting the compressors to permit
warming by the crankcase heaters.
AFTER 24 hours, continue with the procedures below.
CONFIRM THE INPUT POWER PHASE SEQUENCE —
The input power phase rotation sequence must be L1-L2-L3 =
ABC (or forward or clockwise) as indicated with a phase
rotation meter. Incorrect input phase rotation will cause the com-
pressors to rotate in reverse, which results in no cooling capacity.
If the compressor is rotating in the wrong direction, it may:
emit increased noise; shut down due to internal overload
protection; have only a small decrease in suction pressure when
it starts; or have only a small increase in discharge pressure
TEMP TEMP RESISTANCE
(C) (F) (Ohms)
–40 –40 335,651
–35 –31 242,195
–30 –22 176,683
–25 –13 130,243
–20 –4 96,974
–15 5 72,895
–10 14 55,298
–5 23 42,315
032 32,651
541 25,395
10 50 19,903
15 59 15,714
20 68 12,494
25 77 10,000
30 86 8,056
35 95 6,530
40 104 5,325
45 113 4,367
50 122 3,601
55 131 2,985
60 140 2,487
65 149 2,082
70 158 1,752
TEMP TEMP RESISTANCE
(C) (F) (Ohms)
–40 –40 167,835
–35 –31 121,098
–30 –22 88,340
–25 –13 65,121
–20 –4 48,487
–15 5 36,447
–10 14 27,648
–5 23 21,157
0 32 16,325
5 41 12,697
10 50 9,952
15 59 7,857
20 68 6,247
25 77 5,000
30 86 4,028
35 95 3,265
40 104 2,662
45 113 2,183
50 122 1,801
55 131 1,493
60 140 1,244
65 149 1,041
70 158 876
75 167 740
80 176 628
IMPORTANT: On VAV units, fan rotation direction
can NOT be used for the phase sequence check; fan
rotation for VAV units with a variable speed drive is
independent of the unit input wiring sequence.