Carrier 38APD025-100 Air Conditioner User Manual


 
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53380003-01 Printed in U.S.A. Form 38AP-1T Pg CL-1 210 11-09 Replaces: New
START-UP CHECKLIST FOR 38AP SPLIT SYSTEM CONDENSING UNIT
(Remove and use for Job File)
I. Project Information
JOB NAME ______________________________________________________________________________
ADDRESS _______________________________________________________________________________
CITY ____________________________________________ STATE _______________ ZIP______________
INSTALLING CONTRACTOR ________________________________________________________________
SALES OFFICE ___________________________________________________________________________
START-UP PERFORMED BY ________________________________________________________________
Design Information
UNIT MODEL ______________________________ SERIAL ________________________________
II. Preliminary Equipment Check
IS THERE ANY PHYSICAL DAMAGE? YES NO
DESCRIPTION ____________________________________________________________________________
________________________________________________________________________________________
1. UNIT IS INSTALLED LEVEL AS PER THE INSTALLATION INSTRUCTIONS.
YES NO
2. POWER SUPPLY AGREES WITH THE UNIT NAMEPLATE.
YES NO
3. ELECTRICAL POWER WIRING IS INSTALLED PROPERLY.
YES NO
4. UNIT IS PROPERLY GROUNDED.
YES NO
5. ELECTRICAL CIRCUIT PROTECTION HAS BEEN SIZED AND INSTALLED PROPERLY.
YES NO
6. ALL TERMINALS ARE TIGHT.
YES NO
7. ALL PLUG ASSEMBLIES ARE TIGHT.
YES NO
8. ALL CABLES AND THERMISTORS HAVE BEEN INSPECTED FOR CROSSED WIRES.
YES NO
9. ALL THERMISTORS ARE FULLY INSERTED INTO WELLS.
YES NO
10. MOTORMASTER IS INSTALLED ON FAN 1.
YES NO
11. SENSORS (RAT, SAT, SPT) FOR CONTROL TYPES 3, 4, AND 5 ARE INSTALLED.
YES NO
12. LONG LINE OPTION KIT IS INSTALLED, IF NEED.
YES NO
CAPACITY OAT
SUPPLY AIR
TEMPERATURE
RETURN AIR
TEMPERATURE
COIL SIZE
(sq ft)
COIL
CIRCUITING
CFM
SUCTION LINE
DIAMETER
LIQUID LINE
DIAMETER
LINE LENGTH
DOUBLE RISER
(Y/N)
CV/VAV
CONTROL
TYPE (1-9)
ELEVATION DELTA
BETWEEN
INDOOR/OUTDOOR