Carrier 38APD025-100 Air Conditioner User Manual


 
13
Legend and Notes for Fig. 4-10
LEGEND NOTES:
1. Factory wiring is in accordance with UL (Underwriters Labora-
tories) 1995 standards. Any field modifications or additions
must be in compliance with all applicable codes.
2. Use 75 C minimum wire for field power supply.
3. All field interlock contacts must have a minimum rating of
2 amps at 24-vac sealed. See field interlock wiring.
4. Compressor and fan motors are thermally protected. Three-
phase motors protected against single-phase conditions.
5. Terminals 13 and 14 of LVT are for field connection of remote
on-off. The contact must be rated for dry circuit application
capable of handling a 5-vdc, 1 mA to 20 mA load.
6. For 500 series unit operation at 208-3-60 line voltage, TRAN1
primary connections must be moved to terminals H3 and H4.
7. For 575-3-60 units, fan circuit breakers FCB1 and FCB2 are
replaced with fuse blocks FB1 and FB2.
8. For units with low ambient Motormaster
®
V factory-installed
option or field-installed acessory, fan contactors FC1 and FC2
are replaced with fan relays FR1 and FR2.
9. MP-A1 not used in the following units:
070-100: 400-v, 460-v units without digital scroll
10. MP-A2 not used in the following units:
070-100: 400-v, 460-v
11. MP-B1 not used in the following units:
070: all units
080-100: 400-v, 460-v
12. MP-B2 not used in the following units:
070: all units
080-100: 400-v, 460-v
13. MP-A3 not used in the following units:
090,100: 400-v, 460-v
14. MP-B3 not used in the following units:
070: all units
080-100: 400-v, 460-v
15. Jumper plug required when modular motor protector is not
used.
ACCSY Accessory
ALM Alarm
AMPS Amperes
AUX Auxiliary
C—Contactor
CB Circuit Breaker
CCB Compressor Circuit Breaker
CCH Crankcase Heater Relay
CH Crankcase Heater
COMP Compressor
CSB Current Sensor Board
CXB Compressor Expansion Module
DGS Digital Scroll
DPT Discharge Pressure Transducer
DTT Discharge Temperature Thermistor
DUS Digital Unloaded Solenoid
EMM Energy Management Module
EQUIP GND Equipment Ground
FB Fuse Block
FC Fan Contactor
FCB Fan Circuit Breaker
FIOP Factory-Installed Option
FR Fan Relay
FS Fan Status
FU Fuse
GND Ground
HPS High Pressure Switch
LLSV Liquid Line Solenoid Valve
LVT Low Voltage Terminal
MBB Main Base Board
MLV Minimum Load Valve
MM Motormaster
MP Modular Motor Protector
NEC National Electrical Code
OAT Outdoor Air Thermistor
OFM Outdoor Fan Motor
OPT Option
PL Plug
RAT Return Air Temperature
RGT Return Gas Temperature
RLY
Relay
SAT Supply Air Temperature
SEN Sensor Terminal Block
SET Set Point Terminal Block
SPT Suction Pressure Transducer
SW Switch
TB Terminal Block
TEMP Temperature
TRAN Transformer
UPC Unitary Protocol Converter
Y—Cool Stage