Bosch Power Tools 2000 Home Security System User Manual


 
2000 Series | Program Entry Guide | 14.0 User Test EN | 57
Bosch Security Systems | 7/05 | 35114F
14.0 User Test
If the user presses [1] at the keypad and then enters
their passcode, the system performs a user test.
Prompts 1 to 3 tell the system what functions to
perform for the User Test.
1 User Tst, Bell
Default:
No
Selection:
Yes, No
0 No
1 Yes
Setting the
Usr Tst, Bell
prompt to Yes makes a Bell
Test part of the User Test. The system activates the
Alarm Output (Terminals 4 and 5) for 3 seconds. Light
1 on the keypad flashes for the duration of the test.
Set this prompt to Yes for UL 1023,
Household Fire systems.
2 User Tst, Battery
Default:
No
Selection:
Yes, No
0 No
1 Yes
Setting the
Usr Tst, Battery
prompt to Yes makes a
Battery Test part of the User Test. Pressing [1] causes
the system to run solely on battery power for 4
minutes. Light 1 flashes while the control panel is on
battery power. If the battery voltage falls below 12.1
VDC during that 4 minutes, the system restores AC
power and displays a system trouble at the keypad by
flashing the OK light. Refer to System Troubles in the
User Guide.
The system sends a Low Battery Report to the
receiver.
Users can end the test by pressing the [CLEAR] key.
Set this prompt to Yes for UL 1023,
Household Fire systems.
3 User Tst, Comm
Default:
No
Selection:
Yes, No
0 No
1 Yes
Setting the
Usr Tst, Comm
prompt to Yes makes
a Communication Test part of the User Test.
When the user presses [1] and enters a passcode,
the system sends a Test Report to the receiver.
Light 1 flashes during the test. If the system fails to
communicate with the receiver, the system goes
into communication failure and displays a system
trouble at the keypad by flashing the OK light.
Refer to Check System in the User Guide.
The system makes five attempts to send the report
if only one phone number is programmed. It
makes ten attempts if two numbers are
programmed. Refer to
Phone 1, Phone 2