Bosch Power Tools 2000 Home Security System User Manual


 
2000 Series | Program Entry Guide | 11.0 Point Codes EN | 40
Bosch Security Systems | 7/05 | 35114F
Table 5: continued
Display Selection Description
9 Controlled, Part, No
Delay
When control panel is All or Part On (armed), short or open causes alarm
response.
Part points must be normal (not faulted) or bypassed before control panel
can be Part armed.
If an alarm occurs on these points within 2 minutes of a closing (exit time
expired, Excursion/Exit included), the system sends a RECENT CLOSING
message with the Alarm Report.
If these points are faulted at the end of exit delay, the system waits a period
equal to entry delay before sending an Alarm Report. If the system is not
turned off, it sends an EXIT ERROR message with the Alarm Report.
Missing Controlled points generate an alarm response when on, a trouble
response when off.
RF Tamper for a Controlled point generates an alarm response when on, a
trouble response when off.
A Keyswitch Shorting then restoring Keyswitch points toggles the control panel from All
(or Part) On to off, off to All On.
The trouble option (refer to Section 11.3 Digit 3, Point Options)determines
how Keyswitch points respond to opens when the system is off. When the
system is All or Part On, an open produces an alarm response. A keyswitch
always causes a trouble condition if it is opened in the off state, regardless
of the value programmed in Digit 3.
If an alarm occurs on these points within 2 minutes of a closing (exit time
expired, Excursion/Exit included), the system sends a RECENT CLOSING
message with the Alarm Report.
Missing Keyswitch points generate an alarm response when on, a trouble
response when off.
RF Tamper for Keyswitch points generates an alarm response when on, a
trouble response when off.