Bosch Power Tools 2000 Home Security System User Manual


 
2000 Series | Program Entry Guide | 11.0 Point Codes EN | 48
Bosch Security Systems | 7/05 | 35114F
11.6 Recommended Point Codes
Table 10 through Table 16 show some recommended
point codes. Many other point code options are
available. You can create custom point functions using
the many point features available. Be sure to
thoroughly test any point code to be certain the system
functions as you expect.
Table 10: Smoke Detector (trouble on open,
alarm output)
Reports Local
Alarm verification (Pt 1 only) 260## 250##
No verification 160## 150##
Cross point 168## 158##
Partner point 16C## 15C##
RF point 160## 150##
Table 11: Door with Entry/Exit Delay (swinger
bypass, alarm output, alarm report
delay)
Reports Local
Delay on Open
Trouble on Short
882## 852##
Delay on Short
Trouble on Open
881## 851##
Delay on Open or Short
No Troubles
880## 850##
RF point 880## 850##
Table 12: Door or Window with No Entry/Exit
Delay (swinger bypass, alarm output,
alarm report delay)
Reports Local
Trouble on Short 982## 952##
Trouble on Open 981## 951##
No Troubles 980## 950##
RF point 980## 950##
Table 13: Garage Door with Extended Entry/Exit
Delay (swinger bypass, alarm output,
alarm report delay)
Reports Local
Trouble on Short B82## B52##
Trouble on Open B81## B51##
No Troubles B80## B50##
RF point B80## B50##
Table 14: Motion Detector (swinger bypass,
alarm output, alarm report delay)
Reports Local
Trouble on Short 782## 752##
Trouble on Open 781## 751##
No Troubles 780## 750##
Cross point
Trouble on Short
78A## 75A##
Cross point
Trouble on Open
789## 759##
Cross point
No Troubles
788## 758##
Partner point
Trouble on Short
78E## 75E##
Partner point
Trouble on Open
78D## 75D##
Partner point
No Troubles
78C## 75C##
RF point 780## 750##
Table 15: Tamper (swinger bypass, alarm output,
alarm report delay)
Reports Local
Trouble on Short 782## 752##
Trouble on Open 781## 751##
No Troubles 780## 750##
RF point 780## 750##