Bosch Appliances D1260 Home Security System User Manual


 
D1260/D1260B | Owner's Manual | Part III: Advanced Commands - FIRE TEST ? (COMMAND + 5 + 8)
Bosch Security Systems | 9/04 | 50410D 61
4. The current state of the area is displayed for 3
seconds before returning to idle text.
FIRE TEST ? (COMMAND + 5 + 8)
Use this function to test fire points and other 24-hour
points to be certain they function properly. You can
review both the tested and untested points at your
command center to help pinpoint any problems.
Upon initiation, the fire test will test the fire bell
pattern on the bell output and ring the command
center fire bell for 2 seconds. The AC will be disabled
for 4 minutes in order to test the system’s battery
power. If the battery cannot maintain the system for
the 4-minute period, the command center will appear
to go dead. If this happens, contact your security
company. At the end of the 4-minute period, AC is
returned to the system and the panel restores. A
message will be sent to your security company upon
initiation and completion of the Fire Test. During the
Fire Test, no 24-hour alarms will be sent to your
security company.
If there is no activity on the system for 20 minutes, the
system will automatically exit from the Fire Test.
Using Fire Test:
1. Ensure your keypad shows idle disarmed text.
2. Press the COMMAND key. The display shows
*System Command*
.
3. Press the 5 key and then the 8 key.
If you prefer, you may use the Command
Menu in place of steps 2 and 3 to initiate
this function.
Press the MENU> soft key to enter the
Command Menu.
Press NEXT> soft key repeatedly.
When you reach the FIRE TEST ?>
prompt, press its adjacent soft key.
4. When the display shows
### points remain to
be tested
you can begin. (### is the number of
points).
Test each point by first activating the detection
device to fault the point.
If you know the point number, you can
enter it by pressing its number key and
then the ENTER key.
The display will change to show the point
that was entered. If the point is invalid the
message “Invalid Point” or “This is not a
valid walk point” appears.