American Power Conversion FM Air Conditioner User Manual


 
41NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting
Component name. Scroll through the components to view the maintenance intervals:
• Blower 1
• Blower 2
Heater
• Humidifier
Variable Frequency Drive 1 (VFD 1)
Variable Frequency Drive 2 (VFD 2)
Compressor 1
Compressor 2
Alarm. Set the number of operating hours (in 100-hour increments) at which you want an alarm to occur.
Set this to remind you of maintenance milestones.
Alarm delay
Path: Main > Setup > System # > Alarms > Alarm Delays
The alarm delay is the period between start-up and the enabling of alarms. The delay allows the modes
(Cool, Reheat, Dehumidify, and Humidify) to take effect before alarms occur.
Temperature Delay. Set the temperature alarm delay. The maximum delay is 999 seconds (16 minutes,
39 seconds).
Humidity Delay. Set the humidity alarm delay. The maximum delay is 999 seconds (16 minutes, 39
seconds).