American Power Conversion FM Air Conditioner User Manual


 
NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting8
Start the System
Path: Main Menu > On/Off
To start the System, select the On/Off option on the main menu and change the setting to On. The
System will run according to the current settings under Control Environment.
Change settings
To change a setting, use the up or down arrow keys to move the selector arrow to the setting, and press
the
ENTER key.
List of choices. If the setting is a list of choices, an input arrow is displayed next to the setting. Press
the up or down arrow key to make your selection. Press the
ENTER key to save the setting and exit from
input mode. Press the
ESC key to exit without saving.
Numbers or text fields. If the setting is a number or text field, use the arrow keys to select the value
for the first character, and press the
ENTER key to move to the next character position. Repeat this
procedure to select and set each character. After the last character is set, press the
ENTER key to save the
setting and exit from input mode. Press the
ESC key to exit without saving.
Stop the System
Path: Main Menu > On/Off
To stop the System, select the On/Off option on the main menu and change the setting to Off.
Note: Change the setting to Off to shut down all modes of operation and the blower fan; the
display interface and the controller will continue to receive power.
For Systems with electric reheat, the blower fans may continue to operate for up to 60 seconds
to purge heat from the System.
Factory default settings
All Module settings are controlled through the display interface on the front of the Main Module for each
System. The factory default temperature is set at 22.2°C (72°F ) in the cooling mode, and 20°C (68°F ) in
the reheat mode. The default deadband is set at 1.1°C (2°F).