American Power Conversion FM Air Conditioner User Manual


 
NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting26
Action. Set the System controller to respond to the change of status for an input in one of the following
ways:
Map Description/Function
Status Only Displays the event on the Active Alarms screen. Status-only
events are not logged.
Minor Alarm Activates the Warning LED and the alarm beeper. It also creates
an entry in the event log.
Major Alarm Activates the Alarm LED and the alarm beeper. It also creates an
entry in the event log.
Remote Run/Stop Shuts down the Modules normally, waiting for delay timers.
Nonessential Lockout Deactivates modes set as nonessential and continues operation.
Immediate Shutdown Shuts down the Modules immediately. It does not wait for the
blower delay or compressor timers.