American Power Conversion FM Air Conditioner User Manual


 
NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting28
Module Configuration
The Module configuration settings define which components are available and how the Module should
operate.
Caution: The settings in the Module Configuration menu are defined at the factory. Changing
the settings incorrectly can cause serious malfunctions and damage to your System. Only
qualified service personnel should make changes to these settings.
Configure Module
Paths: Main > Setup > Module > Main Module > Module Config > Config Module
Main > Setup > Module > Expansion Module 1 > Module Config > Config Module
The Config Module menu settings define the optional equipment available in the Module.
Output Cap – Indicates the output capacity of the Module, in kilowatts.
Heater – Indicates the type of heating equipment installed to run the reheat mode.
Humid – Indicates the type of humidifier equipment installed to run the humidification mode.
Conds Pump – Indicates the presence of a condensate pump. The pump feeds the condensate
from the reservoir into the drain.
Blower – Indicates the type of blower controller for this Module.
ElecHeater Cap – Indicates the capacity of the electric heater.
Alarm detectors
Paths: Main > Setup > Module > Main Module > Module Config > Set Alarm Detectors
Main > Setup > Module > Expansion Module 1 > Module Config > Set Alarm Detectors
The Set Alarm Detectors settings indicate the presence of sensors in the Modules.
Smoke – Indicates whether a smoke detector is installed in the Module.
Fire – Indicates whether a fire detector (thermal sensor) is installed in the Module.
Note: Thermal sensors for fire detection are not intended for personnel safety.
The devices are intended to supplement, not replace, building fire detection systems.
Water – Indicates whether water leak detectors (loop detectors) are installed in the Module.