American Power Conversion FM Air Conditioner User Manual


 
25NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting
Contacts and Relays
The System can monitor external contact closure events for the following applications:
Magnetic contact switches
Window foil
Tamper switches
Heat detectors
• Water sensors
Pressure sensors
Building smoke and fire detection systems
You can set input contacts to cause alarm conditions based on their current state and a user-defined
normal state. Output contacts can map internal alarms and events to outside devices.
See the NetworkAIR FM DX 60 Hz Installation manual for instructions on connecting contacts
and relays to your Programmable Customer Input/Output Module (PCIOM).
Input contacts
Path: Main > Setup > System # > Input/Output > Input Contacts
Each Main Module supports up to 16 user-defined input contacts. Each contact monitors a sensor and
responds to changes in the state of the sensor (open or closed).
Name. Provide a unique name for each input contact.
Normal. Choose the normal state of the sensor. If the state changes, the controller takes the action
defined by the Alarm Map setting.
Delay. Set how long the contact should be out of its normal state before the controller takes action
(controlled by the Alarm Map setting).
Input: 01of16
Name: Input1
Normal: Open
Status: Open
na0423a
Delay: 030 s
Action:
Major Alarm
na0424a