American Power Conversion FM Air Conditioner User Manual


 
NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting20
Building management
Path: Main > Setup > System # > System Config > Building Management
If you are using a building management system with your Module, you must set the following values:
Address. The address of the Main Module on the RS-485 bus.
Baud Rate. The baud rate for the RS-485 bus.
Parity. The parity for the RS-485 bus.
Stop Bits. The stop bits for the RS-485 bus.
See the NetworkAIR FM DX 60 Hz Installation manual to wire the electrical connections of
the building management system to the RS-485 bus of the Module.
Sensor setup
Path: Main > Setup > System # > System Config > Sensor Setup
Specify the set of sensors the Module will use to calculate the environmental control demands.
Temp/Hum Snsrs. Choose the set of temperature and humidity sensors the controller will use when
determining the need for environmental control. The return sensors and the remote sensor string are
available.
Note:
Any optional remote temperature and humidity probes installed must be supported by the
NetworkAIR FM DX.
Dflt Snsrs. Choose the sensor group that the System will use when the System settings are reset to their
default values.
Rmt Snsr Data. When determining the environmental controls, choose the measurement from the
remote sensors for the controller to use.
Max—Use the maximum value reported by a sensor on the string.
Avg—Use the average reported values of all of the sensors on the string.