Modes
Path: Main > Control Environment > Modes
Enable and disable the modes of operation. The four modes are:
• Cool
Reheat
• Dehumidify
• Humidify
Modes can only be enabled or disabled using the service password.
Essential functions
Path: Main > Control Environment > Essential Functions
Designate each mode as either essential or nonessential. The modes
marked as nonessential are disabled when an alarm or event occurs that
requires all nonessential operations to be stopped (nonessential
lockout).
See “Input contacts” on page 25 for a table with descriptions of how you can set up
nonessential lockout events that occur when an input contact becomes active.
Cool: Enabled
Reheat: Disabled
Dehumid: Enabled
Humidify: Enabled
na0430a
Cool: Essential
Reheat: Nonessent.
Dehumid: Nonessent.
Humidify:Nonessent.