• Normal standby current - approximately 4.0 mA
• Standby voltage - 25VDC maximum, 13.4 minimum
• Maximum short circuit current - approximately 36mA
• Maximum Impedance for Alarm - 1400 ohms
• Normal supervisory current - approximately 4mA
• Low current trouble activation - approximately 3.3mA
• Alarm activation current - approximately 10mA
• Ripple voltage - .4 VDC
• Maximum operating voltage range: 22.5 - 25.9V DC
Frequency - continuous
* In programs 6-9, Zone 1 is a normally closed zone for Firecycle
®
Detectors
Dedicated Supervisory Zones
• For dry contact supervisory devices such as tamper, low air, or high air switches
• 2 Class B Style B circuit, latching
• Power limited, current limited
• End-of-Line resistance - 5.1K ohms
• Ripple Voltage - .1 VDC
• Frequency - continuous
Maximum voltage - 25VDC
• Maximum short circuit current - approximately 36mA
• Maximum line resistance - 100 ohms
• Normal supervisory current - approximately 4mA
• Low current trouble activation - approximately 3.3mA
• Supervisory current condition - approximately 10mA
(Does not include power for any auxiliary devices)
Noti cation/Release Circuits
The output circuits of the VFR-400 are Non-coded. This allows the use of visual and audible appliances on the same circuit. If
temporal noti cation appliances are required for evacuation, selectable tone appliances such as the AMSECO H24W horn or
SH24W Series strobe/horns or a temporal module such as AMSECO TMP1-3A or equivalents should be used.
The noti cation outputs do not provide synchronization. If synchronization is required, use AMSECO SMD10-3A
synchronization module or equivalent, as identi ed on page 55. The noti cation appliances shall be compatible with the sync
module selected. The current requirements of the appliances, wire gauge, and length of wire run determine the maximum
number of appliances that can be connected to one NAC and/or sync module. The maximum cannot exceed 1 amp or whatever
the sync module selected can support, whichever is lower. The sync module shall be installed as per manufacturers instructions.
Equivalent sync modules are shown on page 55.
• 4 Class B Style Y (Class A Style Z module available for noti cation)
• Reverse polarity upon activation
• Power limited, Current limited
• 24 VDC Regulated, rated 1 amp each, 2.5 amps total for all 4 circuits
• End-of-Line-Resistor - 5.1k ohms
• Frequency - continuous
• Maximum voltage - 27 VDC
• Ripple voltage - .3 VDC
• Maximum resistance for outputs programmed as RELEASING:
1 divided by the current draw of the solenoid when activated
• Normal standy supervisory current - approximately .38mA
Low current trouble activation - .11mA
• Maximum impedance - 5 Ohms
• High current trouble activation - .63ma
Low/Missing Battery
Causes battery and system trouble if battery falls below 22 volts. Battery circuit is fused and reverse polarity protection is provided.
Input Power
• Universal Input 120VAC, (60 Hz, 165VA) or 220VAC, (50 Hz, 185VA) 15 Amp Branch Line overcurrent
protection required.
• System trouble is also generated if voltage drops below 102V.
Backup Power Requirements
• VFR-400 - Standby 121 mA, alarm 274 mA at 24VDC