Viking VFR-400 Smoke Alarm User Manual


 
46
VFR-400 • 5403548 • REV D • 10/07
Soak Timer Description
This allows the user to select the amount of time the release circuit on output #3 will stay activated after the Firecycle zone
restores to normal. The available times are 30, 60, 90 seconds, 2-20 minutes in 1 minute incriments, or continous.
After describing all initiating zones or skipping to the next function, the following will appear in the display window:
SET Press the SET button to set the description displayed.
SELECT Press the SELECT button to scroll through the ve descriptions.
(Supervisory, Valve Tamper, Low Air, High Air)
FUNCTION Press the bottom button to skip to the next function.
After Selecting SUP 1, the following will appear in the display window.
SET Press the SET button to set the description displayed.
SELECT Press the SELECT button to scroll through the four supervisory descriptions.
(Supervisory, Valve Tamper, Low Air, High Air)
FUNCTION Press the bottom button to skip to the next function.
After describing what the supervisory zone is to be or skipping to the next function, the following will appear
in the display window:
Output Description
This allows the user to describe the functions of the output circuits. Four descriptions are available:
1) ALARM INDICATING - Noti cation appliances include bells, horns, strobes and other appliances used to indicate an alarm.
2) RELEASING - Releasing appliances include solenoids and other electrically compatible devices.
3) SUPERVISORY BELL - Appliances on this circuit are used to indicate the presence of a supervisory condition. Any zone
programmed as LOW AIR ALARM, SUPERVISORY, TAMPER, HI AIR or LOW AIR is automatically mapped to this output.
4) TROUBLE BELL - Appliances on this circuit are used to indicate the presence of a trouble condition.
The user should describe each output circuit in the same manner as the initiating circuit was described by pressing the SELECT
button to select and the SET button to set the desired function.
SET Press the SET button to set the description displayed.
SELECT Press the SELECT button to scroll through the descriptions.
FUNCTION Press the bottom button to skip to the next function.
SUPERVSRY 1 ZONE
SUPERV I SRY
SUPERVSRY 2 ZONE
SUPERV I SRY
OUT PUT # 1
INDICATING