Viking VFR-400 Smoke Alarm User Manual


 
42
VFR-400 • 5403548 • REV D • 10/07
XX = Cross-Zoned
NOTES:
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (Release
Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.
2. Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.
3. Leave EOLR (provided) on all unnused circuits.
4. See the instruction manual for circuit information, panel limits, and battery sizing.
5. For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.
6. See instruction manual for proper programming.
7. See instruction manual for list of compatible smoke detectors.
8. See speci c system type data page for proper pressure switch settings.
PROGRAM #12
For One Sprinkler System
Viking Sprinkler
System Types
2 Cross Release
Zones, Water ow
Zone, and Manual
Release Zone
1. Single Interlocked Preaction System with Electric Release
2. Deluge System with Electric Release
3. Non-Interlocked Preaction system with Electric Release
4. Double Interlocked Preaction System with Electric/Pneu-Lectric Release
OUTPUTS
(Indicating Circuits)
ZONES (Initiating Circuits)
SUP 1 SUP 2 #1 #2 #3 #4
Valve Tamper
Supervisory Zone
Low Air
Supervisory Zone
Conventional
Detection Zone
Conventional
Detection Zone
Water ow
Zone
Manual
Release Zone
#1 General Alarm X X X
#2 Water ow X
#3 Release Solenoid X X X X X
#4 Supervisory Bell X X
OPERATION DESCRIPTION
Inputs: 2 Conventional Detection zones, 1 Water ow zone, 1 Manual Release zone, 2 Supervisory zones
Outputs: 1 General Alarm, 1 Water ow, 1 Release Solenoid, 1 Supervisory Bell
Operation: Simultaneous activation of both the Conventional Detection zone #1 and the Conventional Detector
zone #2 will activate output #3 (Release Solenoid) and output #1 (General Alarm)
Activation of Conventional Detection zone #1 will activate output #1 (General Alarm)
Activation of Conventional Detection zone #2 will activate output #1 (General Alarm)
Activation of Water ow zone #3 will activate output #2 (Water ow)
Activation of Manual Release zone #4 will activate output #3 (Release Solenoid) and output #1
(General Alarm)
Activation of Valve Tamper Supervisory zone #1 or Low Air Supervisory zone #2 will activate output
#4 (Supervisory Bell)