Viking VFR-400 Smoke Alarm User Manual


 
34
VFR-400 • 5403548 • REV D • 10/07
PROGRAM #8
For One Sprinkler System
Viking Sprinkler
System Types
1 Release Zone
and Manual
Release
1. FIRECYCLE III Deluge Multicycle System
OUTPUTS
(Indicating Circuits)
ZONES (Initiating Circuits)
SUP 1 SUP 2 #1 #2 #3 #4
Supervisory Zone Valve Tamper
Supervisory Zone
FIRECYCLE
Detector Zone
Supervisory
Zone
Water ow
Zone
Manual
Release Zone
#1 General Alarm X X X
#2 Supervisory Bell X X X
#3 Release Solenoid X X
#4 N/O Solenoid X X
OPERATION DESCRIPTION
Inputs: 1 FIRECYCLE Detection zone, 1 Supervisory zone, 1 Water ow zone, 1 Manual Release zone, 2
Supervisory zones
Outputs: 1 General Alarm, 1 Supervisory Bell, 1 Release Solenoid, and 1 N/O Solenoid
Operation: Activation of FIRECYCLE Detector zone #1 will activate output #1 (General Alarm), output #3 (Release
Solenoid) and output #4 (N/O Solenoid)
Activation of Supervisory zone #2 will activate output #2 (Supervisory Bell)
Activation of Water ow Alarm zone #3 will activate output #1 (General Alarm) and output #4 (N/O
Solenoid)
Activation of Manual Release zone #4 will activate output #1 (General Alarm) and output #3 (Release
Solenoid)
Deactivation of FIRECYCLE Detector zone #1 will start soak timer, when timer cycle is complete the
output #3 (Release Solenoid) is deactivated.
Activation of Supervisory zone #1 or Valve Tamper Supervisory Zone #2 will activate output #2
(Supervisory Bell)
NOTES:
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (N/O
Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.
2. Polarity is shown on indicating circuits in normal (no alarm) condition. Polarity reverses when ouptut is activated.
3. Leave EOLR (provided) on all unnused circuits.
4. See the instruction manual for circuit information, panel limits, and battery sizing.
5. For wire routing instructions through the releasing panel, see Note 3 on page 56 of the instruction manual.
6. See instruction manual for proper programming.
7. See speci c system type data page for proper pressure switch settings.
8. Connect EOL resistor after last FIRECYCLE detector on return line to common terminal in FIRECYCLE Detector zone #1.
9. Set the soak timer to desired duration period. Factory setting is continuous. Recommend 60 seconds minimum.
10. Loss of DC power below 20 volt causes output #3 (Release Solenoid) and output #4 (N/O Solenoid) to drop out.
11. Use only Viking FIRECYCLE detectors on FIRECYCLE Detector zone #1.