18
VFR-400 • 5403548 • REV D • 10/07
Outputs Alarm 24VDC Bells, Horns, Strobes, to indicate an alarm condition.
Release Solenoid Valve, Squib, Releasing Mechanism
Supervisory 24VDC Bells, Horns, Strobes, to indicate a supervisory condition.
Trouble 24VDC Bells, Horns, Strobes, to indicate a trouble condition.
To program the VFR-400 to operate with one of the following 12 standard programs:
1) Press SELECT button to scroll to the program number (#1 thru #12) you desire.
2) Press SET button.
3) Turn to page 48 to program the banner message and to fi nish programming the panel.
SET After selecting the proper program number, press the SET button to set the program and move to the next function.
SELECT Press the SELECT button to scroll through the programs.
FUNCTION Press the bottom button to skip to the next function.
After selecting the desired program number with the middle button, SET must be pressed to set the program.
When the Firecycle programs (6-9) are selected, only outputs #3 and #4 can be selected as releasing.
If the Firecycle feature is used, Firecycle heat detectors must be connected to Zone 1. Zone 1 follows the status of the Firecycle
detector. When the detector resets, a soak timer is initiated. The default soak timer is continuous. The soak timer is user
selectable to 30, 60, or 90 seconds or 2 - 20 minutes in 1 minute increments.