One Man Walktest
This display allows the user to select system mode NORMAL or ONE MAN WALKTEST by pressing the SELECT button to
toggle back and forth from NORMAL to ONE MAN WALKTEST. When the desired mode is displayed, press the SET button.
If ONE MAN WALKTEST is selected for test purposes, the display must be restored to the NORMAL setting after the test is
completed by toggling to it using the SELECT button.
SET After selecting NORMAL or ONE MAN WALKTEST, press the SET button to set that mode.
SELECT Press the SELECT button to toggle between NORMAL and CROSS ZONED.
FUNCTION Press the bottom button to skip to the next function.
After selecting the operating mode or pressing the FUNCTION button a display similar to the following will appear in the display
window:
VFR-400 Standard Program Information
The VFR-400 has 12 standard programs which are detailed in the following pages. Selecting one of these programs will
automatically program every function of the panel except the custom banner and zone message functions.
Notes:
The release discharge time is continuous for all programs not employing the Firecycle feature. The default soak timer for the
Firecycle feature is continuous.
The following is an explanation of how the various programs operate and information about the types of
devices that are to be connected to the input and output zones. If none of the standard programs are acceptable for the installation
required, select the custom program #0 then press the SET button. This will allow the user to custom program the panel. Turn to
page 45 for custom program information.
Type Description
Alarm Zones Detection Smoke Detectors, Spot Type Heat Detectors
Water ow PS10 Pressure Switch
Linear Heat Cable Type Heat Detectors
Manual Release Pull Stations
Firecycle Viking normally closed heat detectors
Supervisory Zones Supervisory Valve Tamper, Low Air, High Air, Room Temperature
Low Air supervisory Low Air Switch
High Air High Air Switch
Tamper Valve Tamper Switch
Low Air Alarm * PS10, PS40
* Not available on Supervisory Zones Sup 1 or Sup 2
PROGRAM #1
After 30 minutes of no activity the panel
automatically reverts to normal.