Chapter 3 Termination board wiring
32 BMTK-SVN01D-EN
UCM wiring configurations
The Tracker UCM Comm5 communication-link wiring must be installed
in a daisy-chain configuration (Figure 15 on page 32 and Figure 16 on
page 33).
Figure 15. Daisy-chain configuration for UCM communication-link
wiring (preferred configuration)
Trane UCM
Trane UCM
Trane UCM
Tracker
Controller
Figure Note:
Maximum wire length for daisy-chained wiring is 4593 ft (1400 m).