Trane Building Automation System Thermostat User Manual


 
®
Chapter 3 Termination board wiring
30 BMTK-SVN01D-EN
Table 7. Trane-approved wire suppliers
Supplier Cable type
Number of
pairs
Details
Catalog
number
Connect-Air International
Phone: 1-800-247-1978
FAX: 1-253-813-5699
Web: www.connect-air.com
Level 4
22 AWG
(0.643mm
2
)
1 Shielded plenum
UL type CMP
W221P-2002
Level 4
22 AWG
(0.643mm
2
)
1 Shielded non-plenum
UL type CM
W221P-1003
Windy City Wire
Phone: 1-800-379-1191
FAX: 1-708-493-1380
Web: www.smartwire.com
Level 4
22 AWG
(0.643mm
2
)
1 Shielded plenum
UL type CMP
106500
Level 4
22 AWG
(0.643mm
2
)
1 Shielded non-plenum
UL type CM
107600
Category 4 cable is not the same as Level 4 cable and should not be used. The Echelon Level 4 cable specification was originally
defined by the National Electrical Manufacturers Association (NEMA) and differs from the Category 4 specification proposed
by the Electronic Industries Association/Telecommunications Industry Association (EIA/TIA).