Trane Building Automation System Thermostat User Manual


 
BMTK-SVN01D-EN 15
®
Chapter 2
Termination module
mounting
After unpacking and inspecting the shipment, mount the termination
module. The mounting process for the termination module consists of
selecting a location and mounting the module. This chapter provides
information and procedures that enable you to mount the termination
module.
Select a location for the controller
When selecting a location for the Tracker controller:
Select a location that is in a clean, non-corrosive, indoor environment.
The controller is only intended for indoor installation.
Consider both security and control wire lengths when making the
selection.
Select a location that limits controller access to operating and service
personnel.
Select a location that conforms to the operating environment
described in Table 1 on page 9. The recommended operating environ-
ment will extend the life of the electronic components. Verify that the
location does not subject the controller to extreme operating condi-
tions (including excessive vibration).
CAUTION
Avoid Equipment Damage!
Install the Tracker controller out of direct sunlight. Failure to do so may
cause overheating, which could result in equipment damage.
IMPORTANT
Do not install the Tracker controller near high-power radio signals, elec-
trical switching gear, power buses, large motors, or other sources of
electrical noise. The electrical interference may lead to control malfunc-
tions.
Verify location conformance to controller specifications
Verify that the selected location conforms to the applicable controller
specifications listed in Table 1 on page 9.