Macurco DVP-120 Carbon Monoxide Alarm User Manual


 
Revision 0.07
27
3.3.5 Configure Horn Submenu
The configuration parameters for the horn are the same as those for relays. A horn would not normally require a
minimum on time but this parameter allows a more versatile configuration.
3.3.5.1 Horn Summary
H
o
r
n
4
N
o
r
m
.
O
f
f
D
e
l
a
y
O
n
Figure 3-33 Horn Summary
This display example shows that the horn has been configured to operate Normally Off, with a turn on delay
and no minimum on time.
Notice that the horn number, 4, is underlined. This indicates that the digit keys can be used to jump to a
particular relay, horn or strobe. The relays are numbers 1, 2 and 3; the horn is number 4 and the strobe is 5.
3.3.5.2 Horn Mode
H
o
r
n
N
o
r
m
.
O
f
f
M o
d
e
:
2
Figure 3-34 Horn Mode
This display example shows that the horn is configured to operate in the Normally Off mode. The valid modes
are:
2 Normally Off (default)
3 Normally On
3.3.5.3 Horn Turn On Delay
H
o
r
n
D
e
l
a
y
O
n
(
m
m
:
s
s
)
0
1
:
0
0
Figure 3-35 Horn Turn On Delay
The default turn on delay is one minute and the maximum allowed value is fifteen minutes.
3.3.5.4 Horn Minimum On Time
H
o
r
n
M
i
n
.
O
n
(
m
m
:
s
s
)
0
0
:
0
0
Figure 3-36 Horn Minimum on time
The default minimum on time is zero and the maximum allowed value is fifteen minutes.