Macurco DVP-120 Carbon Monoxide Alarm User Manual


 
Revision 0.07
24
3.3.3 Configure Sensors Submenu
There is a list of parameters for each sensor in the system, either currently wired or configured but presently
disconnected. The left and right cursor keys can be used to move from one sensor to another; doing so always
goes to the first display (summary). The up and down keys will scroll through the parameters for the particular
sensor.
3.3.3.1 Sensor Summary
S
e
n
s
o
r
0
1
C
O
A
:
2
0
0
W
:
5
0
Figure 3-24 Sensor Summary
This display example shows that the sensor on channel 01 has been configured as a Carbon Monoxide sensor
with an Alarm level of 200 ppm and a Warning level of 50 ppm.
Notice that the sensor number, 01 in this example, is underlined. This indicates that the digit keys can be used to
jump to a particular channel, even if there is no sensor connected to the channel. When the first digit is entered,
the display will prompt for the sensor to show.
3.3.3.2 Sensor Type
S
e
n
s
o
r
0
1
C
O
T
y
p
e
:
1
Figure 3-25 Sensor Type
This display example shows that the sensor on channel 01 has been configured as a Carbon Monoxide sensor.
The valid entries for the sensor type are:
1 Carbon Monoxide (CO)
2 Nitrogen Dioxide (NO2)
3 Combustible (EX)
0 None (---)
Setting the sensor type to 0 (zero) will cause the display to ask if the user wants to DELETE the sensor. If the
answer is yes, the configuration record for this sensor channel will be deleted and the channel will no longer be
used to control the ventilation system. If a sensor indicates trouble (or there are wiring problems on a channel),
this will stop any annoying trouble signals for this channel.
When a sensor’s type is changed, the alarm level, warning level and range will be set to the default for the
sensor type.
The following three parameters are not accessible until a sensor type of 1, 2 or 3 is selected.
3.3.3.3 Alarm Set Point
S
e
n
s
o
r
0
1
C
O
A
l
a
r
m
:
_
2
0
0
p
p
m
Figure 3-26 Sensor’s Alarm Level
The default alarm levels for the sensors are:
Carbon Monoxide 200 ppm
Nitrogen Dioxide 5.0 ppm
Combustible 4,000 ppm (10% LEL for methane)
Setting an alarm level of 0 (zero) will disable alarm detection for this particular sensor.