Heat & Glo LifeStyle XLR-PLUS-N-AU Indoor Fireplace User Manual


 
9Heat & Glo • XLR-PLUS-N-AU, XLR-PLUS-PB-AU • 2264-900 Rev. M • 7/12
A. ApplianceCertication C. HighAltitudeInstallations
NOTICE: If the heating value of the gas has been reduced,
these rules do not apply. Check with your local gas utility
or authorities having jurisdiction.
When installing above 2000 ft. (610 m) elevation:
Reduce input rate 4% for each 1000 ft. (305 m) above
2000 ft. (610 m).
D. Non-CombustibleMaterialsSpecication
Material which will not ignite and burn. Such materials are
those consisting entirely of steel, iron, brick, tile, concrete,
slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
StandardTestMethodforBehaviorofMaterialsina
VerticalTubeFurnaceat750ºC(1382°F)andUL763
shall be considered non-combustible materials.
E. CombustibleMaterialsSpecication
Materials made of or surfaced with wood, compressed pa-
per, plant bers, plastics, or other material that can ignite
and burn, whether ame proofed or not, or plastered or
unplastered shall be considered combustible materials.
F. ElectricalCodes
All electrical safety testing has been done following the EN
60335-2-102 standard. Local codes apply.
1
ListingandCodeApprovals
MODELS: XLR-PLUS-N-AU,XLR-PLUS-PB-AU
LABORATORY: SAIGlobal
TYPE: GasSpaceHeatingAppliance
STANDARD:AS4553:2008
The Heat & Glo gas appliances discussed in this Installer’s
Guide have been tested to certication standards and listed
by the applicable laboratories.
This appliance must be installed in accordance with the
rules in force.
NOX Class 5 for G20, NOX Class 5 for G31
B. GasPressureRequirements
Pressure requirements for XLR-PLUS replaces are
shown in table below.
Two taps are provided on the right hand side of the gas
control for a test gauge connection to measure the inlet
and outlet pressures.
The replace and its individual shut-off valve must be dis-
connected from the gas supply piping system during any
pressure testing of the system at test pressures in excess
of 3.4 kPa.
If the replace must be isolated from the gas supply pip-
ing system by closing an individual shut-off valve, it must
be of the handle-less type.
NaturalGas Propane Butane
Inlet Gas Pressure 1.13 - 3.40 kPa 2.75 - 3.40 kPa 2.75 - 3.40 kPa
Outlet (Manifold) Gas Pressure .80 - .95 kPa 2.36 - 2.61 kPa 2.36 - 2.61 kPa
Gas Rate .405
m3
/
h
.134
m3
/
h
.111
m3
/
h
Maximum Gas Consumption 26 MJ/h 26 MJ/h 22 MJ/h
Burner Injector DMS 42 (2.350 mm) DMS .057 (1.450 mm) DMS 55 (1.325)
Pilot Injector Ø .023 (.584 mm) Ø .014 (.356 mm) Ø .010 (.254 mm)
Columns highlighted in gray = The gas control valve supplied with this product is approved for a maximum
inlet pressure of 3.40kPa. For pressures over 3.40kPa, an in line pressure regulator must be installed
upstream from the gas control valve.