21Heat & Glo • XLR-PLUS-N-AU, XLR-PLUS-PB-AU • 2264-900 Rev. M • 7/12
D. MantelandWallProjections
WARNING! Risk of Fire! Comply with all minimum clear-
ances to combustibles as specied. Framing or nishing
material closer than the minimums listed must be construct-
ed entirely of noncombustible materials (i.e., steel studs,
concrete board, etc).
Figure5.3 ClearancesToCombustibleMantelsOrOther
CombustiblesAboveAppliance
Mantels(Combustible/Non-Combustible)
Figure5.4MantelLegorWallProjections
(Acceptableonbothsidesofopening)
UNLIMITED
TOP VIEW
3-1/8 in.
(80 mm)
MINIMUM
FRAMING
1-1/8 in. (30 mm)
3/8 in (10 mm) BUILDING MATERIAL
1-1/2 in. (37 mm)
FrontSideFinishingDetail
Figure5.5FrontSideFinishingDetail
14-1/8 in
(360 mm)
MIN.
12 in. (300 mm)
MAX.
3/8 in. (10 mm)
Thick Wall
Sheathing
MEASUREMENT
FROM TOP OF
FIREPLACE
OPENING
Note:For non-combustible replace nish material (marble,
stone, etc) specications refer to Section 13.
MantelLeg(Combustible/Non-Combustible)
3/8 in. (10 mm) THICK
WALL SHEATHING
3-1/2 in.
(89 mm)
1 in.
(25 mm)
AIR SPACE
NON-COMBUSTIBLE
BOARD SHIPPED
WITH APPLIANCE
1 in. (25 mm)
Figure5.6Non-CombustibleZone
Note:AIR SPACE denoted in Figure 5.6 is dened by the
nailing tabs and top metal standoffs.