27Heat & Glo • XLR-PLUS-N-AU, XLR-PLUS-PB-AU • 2264-900 Rev. M • 7/12
Figure7.5VerticalVentMaximum
Note: If installing a vertical vent/termination off the top of the
appliance, the optional exhaust restrictor may be needed.
V
1
V
1
Max=13.4m(44ft.)
TopVent-VerticalTermination
NoElbows
Note: Use SLP Series
components only.
ExhaustRestrictorInstructions
1. Locate the inner rebox exhaust restrictor. Figure 7.6.
Exhaust restrictors are recommended for these vertically
terminated products which have excessive draft. Exhaust
restrictors will compensate for high draft. and restore vi-
sual ame height. If the vent conguration has a total ver-
tical of 6-1/2 ft. - 44 ft. (2 m - 13.4 m), an exhaust restrictor
may be needed. The exhaust restrictor is located in the
appliance manual bag.
3. Replace existing restrictor with small cut-out restrictor
in manual bag for installations with more than 6-1/2 ft.
(2 m) of vertical piping. See Figure 7.7.
Figure7.6StandardRestrictor
Figure7.7RestrictorwithSmallCut-Out
2. Remove restrictor for XLR-LOGS kit.