Heat & Glo LifeStyle 8000CL-IPI-T Indoor Fireplace User Manual


 
Heat & Glo • 6000CL-IPI-S, 6000CL-IPI-T, 8000CL-IPI-S 8000CL-IPI-T • 2165-900 Rev. S • 9/12
30
H
1
V
1
V
2
TopVent-VerticalTermination(continued)
Figure7.11
TwoElbows
Figure7.10
4. Center the Flue Restrictor on vent and secure in place
by using two self-tapping screws (see Figure 7.10).
5. Reinstall the Exhaust Shield.
3. Match the amount of vertical you have in the system
with the chart to nd the appropriate position to set the
Flue Restrictor (see Figure 7.9).
Figure7.9
1 2 3 4 5
SETTING
1 2 3 4 5
Vertical
TOPVENT REARVENT
NG LP NG LP
4 ft. 1-1
No
Restrictor
No
Restrictor
No
Restrictor
8 ft. 2-2 1-2 1-1
No
Restrictor
15 ft. 3-3 3-2 2-2 1-2
20 ft. 3-3 3-3 3-3 2-3
25 ft. 3-3 3-3 3-3 2-3
30 ft. 3-4 3-3 3-3 3-3
35 ft. 3-4 3-4 3-4 3-3
40 ft. 3-4 3-4 3-4 3-4
V
1
H
1
Maximum V
2
V
1
+ V
2
Min.
Elbow only 2 ft. 610 mm * * *
6 in. 152 mm 6 ft. 1.8 m * * *
2 ft. 610 mm 11 ft. 3.4 m * * *
3 ft. 914 mm 16 ft. 4.9 m * * *
4 ft. 1.2 m 20 ft. 6.1 m * * *
V
1
+ V
2
+ H
1
= 50 ft. (15.2 m) Maximum
*No specic restrictions on this value EXCEPT
V
1
+ V
2
+ H
1
cannot exceed 50 ft (15.2 m)
Note: If the DVP-2SL or DVP-SLP24 adapter is used with
SLP pipe, you MUST subtract one number from the table
above.
Example: Top vent 40 ft vertical with DVP pipe = 3-4
Top vent 40 ft vertical with SLP pipe = 2-3