Hearth and Home Technologies SL-750TR-D Furnace User Manual


 
41
Heat & Glo • SL-550 / 750 / 950TR-D • InD • 2044-985 Rev. M • 10/06
E. Junction Box Installation
F. Wall Switch Installation for Fan (Optional)
Figure 10.6 Junction Box Wired to Wall Switch
If the box is being wired to a wall mounted
switch for use with a fan (See Figure 10.6):
The power supply for the appliance must
be brought into a switch box.
The power can then be supplied from
the switch box to the appliance using a
minimum of 14-3 with ground wire.
At the switch box connect the black (hot)
wire and red (switch leg) wire to the wall
switch as shown.
At the appliance connect the black (hot),
white (neutral) and green (ground) wires
to the junction box as shown.
Add a 1/4 inch insulated female connector
to the red (switch leg) wire, route it through
the knockout in the face of the junction
box, and connect to the top fan switch
connector (1/4 inch male) as shown.
If the box is being wired from the appliance:
Remove the screw attaching the junction
box to the outer shell, rotate the junction box
inward to disengage it from the outer shell
(see Figure 10.5).
Pull the electrical wires from outside the
appliance through this opening into the valve
compartment.
• Loosen the two screws on the Romex
connector (not included with unit), feed the
necessary length of wire through the connector
and tighten the screws.
Make all necessary wire connections to the
receptacle and assemble the receptacle and
cover to the junction box.
WHT
WHT
BLK
BLK
GRN wire
inside box
Copper
ground attached
to GRN screw with
GRN wire
14/2WG
Cover Plate
outside firebox
Romex
Connector
Figure 10.5 Junction Box Detail
Red
Red
BlackBlack
Green
Green
White
White
Red
Black
Green
White
SWITCH BOX
JUNCTION BOX
POWER
SUPPLY WIRES
SWITCH
MINIMUM 14-3 AWG
WITH GROUND
NOTE: Do NOT wire
110VAC to wall switch.