Hearth and Home Technologies SL-750TR-D Furnace User Manual


 
Heat & Glo • SL-550 / 750 / 950TR-D • InD • 2044-985 Rev. M • 10/0634
Installing Wall Shield Firestops and Horizontal Termination Cap (SL Series Pipe ONLY)
Do NOT connect a pipe section to a termination cap without using
the telescoping ue section found on the termination cap.
NOTE: Where required, an exterior wall ashing is available.
When penetrating a brick wall, a brick extension kit is avail-
able for framing the brick.
Installing the Horizontal Termination Cap
Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
Flash and seal as appropriate for siding material at out
side edges of cap.
When installing a horizontal termination cap, follow the cap
location guidelines as prescribed by current ANSI Z223.1
and CAN/CGA-B149 installation codes.
Burn Risk
Local codes may require installation of a
cap shield to prevent anything or anyone
from touching the hot cap.
Figure 8.14 Hole and Vent Pipe
Figure 8.15 Heat Shield, Interior & Exterior Firestops
TRIM HEAT
SHIELDIFTOO
LONG, ADDTO
SHIELDIFTOO
SHORT
WALL SHIELD
FIRESTOP
(EXTERIOR)
WALLSHIELD
FIRESTOP
(INTERIOR)
HEAT SHIELD
ALWAYS maintain speci ed clearances around venting
and restop systems.
• Install restops as speci ed.
Failure to keep insulation or other material away from
vent pipe may cause re.
VENT PIPE
1 in. (25.4 mm)
10 in.
(254mm)
10 in.
(254mm)
For Horizontal Runs - Wall shield restops are REQUIRED on
both sides of a combustible wall through which the vent passes.
NOTE: Model SLK-01TRD does not need an exterior
wall shield restop on an exterior combustible wall.
To install wall shield restops for horizontal runs that pass
through either interior or exterior walls:
Cut a 10 in. x 10 in. (254mm x 254mm) hole for SL-D-
series pipe. The center of the framing hole is one (1) inch
(25.4mm) above the center of the horizontal vent pipe.
• Position the wall shield restops on both sides of the
hole previously cut and secure the wall shield restops
with nails or screws.
The heat shields of the wall shield restops MUST BE
placed towards the top of the hole.
Continue the vent run through the wall shield restops.
Fire Risk.
Explosion Risk.
Do NOT pack insulation or other
combustibles between restops.
Fire Risk
Exhaust Fumes Risk
Impaired Performance of Appliance
Ensure vent components are locked together correctly.
Pipe may separate if not properly joined.
WARNING
WARNING
WARNING
WARNING