Carrier 50SS018-060 Air Conditioner User Manual


 
REQUIRED CLEARANCES TO COMBUSTIBLE MATERIAL in. (mm)
Unit Top ........................................14(356)
Duct Side of Unit ...................................2(51)
Side Opposite Ducts ...............................14(356)
Bottom of Unit .........................................0
Vertical Discharge First 12 in. (305) of Supply Duct ...........1(25)
NECESSARY REQUIRED CLEARANCES in. (mm)
Between Units, Control Box Side .....................42(1067)
Unit and Ungrounded Surfaces, Control Box Side ...........36(914)
Unit and Block or Concrete Walls and Other Grounded
Surfaces, Control Box Side .........................42(1067)
REQUIRED CLEARANCES FOR SERVICING in. (mm)
Evaporator Coil Access Side .........................30(762)
Control Box Access Side ............................30(762)
(Except for Necessary Requirements)
Unit Top ........................................36(914)
Side Opposite Ducts ...............................30(762)
NOTES:
1. Clearances mustbemaintained topreventrecirculation ofair fromoutdoor-
fan discharge.
2. Dimensions in ( ) are in millimeters.
LEGEND
CG Center of Gravity NEC National Electrical Code
COND Condenser REQ’D Required
MAT’L Material
UNIT
50SX
ELECTRICAL
CHARACTERISTICS
UNIT WT CORNER WT (Lb/Kg)
Lb Kg A B C D
042 208/230-1-60, 208/230-3-60, 460-3-60 309 140 84/38 59/27 119/54 47/21
048 208/230-1-60, 208/230-3-60, 460-3-60 340 155 84/38 70/32 133/60 53/24
060 208/230-1-60, 208/230-3-60 359 163 65/30 99/45 120/55 75/34
UNIT
50SX
CENTER OF GRAVITY (in./mm)
XYZ
042 21.0/533 20.1/510 15.4/390
048 21.8/553 19.7/499 15.4/390
060 22.2/565 19.8/503 13.4/340
Fig. 8 Dimensions; Units 50SX042-060 Without Base Rail (cont)
9