Carrier 50SS018-060 Air Conditioner User Manual


 
REQUIREDCLEARANCESTOCOMBUSTIBLEMATERIAL—in.(mm)
Unit Top ................................14(356)
Duct Side of Unit ............................2(51)
Side Opposite Ducts ........................14(356)
Bottom of Unit .................................0
Vertical Discharge First 12 in. (305) of Supply Duct .......1(25)
NECESSARY REQUIRED CLEARANCES — in. (mm)
Between Units, Control Box Side ................42(1067)
Unit and Ungrounded Surfaces, Control Box Side ......36(914)
Unit and Block or Concrete Walls and Other Grounded
Surfaces, Control Box Side ...................42(1067)
REQUIRED CLEARANCES FOR SERVICING — in. (mm)
Evaporator Coil Access Side ...................30(762)
Control Box Access Side ......................30(762)
(Except for Necessary Requirements)
Unit Top ................................36(914)
Side Opposite Ducts ........................30(762)
NOTES:
1. Clearances must be maintained to prevent recirculation of air from
outdoor-fan discharge.
2. Dimensions in ( ) are in millimeters.
LEGEND
CG Center of Gravity NEC National Electrical Code
COND Condenser REQ’D Required
MAT’L Material
UNIT
50SX
CENTER OF GRAVITY (in./mm)
XYZ
024 21.5/546 20.8/528 15.0/380
030 21.7/550 20.7/527 15.0/380
036 20.6/524 20.1/510 15.0/380
UNIT
50SX
ELECTRICAL
CHARACTERISTICS
UNIT WT CORNER WT (Lb/Kg)
Lb Kg A B C D
024 208/230-1-60 290 132 72/33 67/30 104/47 47/21
030 208/230-1-60 293 133 71/32 69/31 105/48 48/22
036 208/230-1-60, 208/230-3-60, 460-3-60 311 142 85/39 59/27 117/53 50/23
Fig. 7 Dimensions; Units 50SX024-036 With Optional Base Rail
7