Carrier 50SS018-060 Air Conditioner User Manual


 
Table 9 Dry Coil Air Delivery* Vertical Discharge (Deduct 10% for 208 v) Unit 50SS
UNIT
SIZE
MOTOR
SPEED
230 AND 460 V VERTICAL DISCHARGE
External Static Pressure (in. wg)
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
018
Low
Watts 230 225 220 210 195 170 —————
Cfm760745725695640540—————
High
Watts ————270235200————
Cfm————850700450————
024
Low
Watts 280 275 265 255 250 245 240 ————
Cfm820810755700660600560————
Med
Watts 365 360 350 345 340 330 320 310 300
Cfm 1025 1010 975 940 900 850 800 720 630
High
Watts 490 480 470 460 445 430 410 390 380
Cfm 1300 1255 1200 1150 1080 1005 915 790 620
030
Low
Watts 460 450 420 400 380 360 335
Cfm 1240 1190 1125 1060 995 920 840
Med
Watts 480 460 435 410 375
Cfm 1280 1200 1115 1020 910
High
Watts —————560530510490460
Cfm—————1270 1180 1080 1000 870
036
Low
Watts 470 460 455 445 430 415 400 380 350
Cfm 1280 1250 1230 1200 1150 1100 1050 980 890
Med
Watts 550 535 520 500 480 460 440 410 385
Cfm 1500 1450 1400 1330 1270 1190 1120 1030 940
High
Watts ————625595550520500470425
Cfm————1540 1440 1325 1220 1110 1000 800
042
Low
Watts 730 700 680 645 615 580 535 490 430
Cfm 1620 1590 1550 1510 1460 1390 1310 1210 1050
High
Watts —————850800750700650610
Cfm—————1780 1670 1550 1400 1230 1050
048
Low
Watts 1080 1040 1020 970 910 840 785 730 680 620 540
Cfm 2100 2090 2080 2060 1980 1900 1810 1710 1590 1450 1200
High
Watts 1230 1190 1125 1060 1010 940 880 820 760 710 660
Cfm 2390 2340 2280 2210 2150 2030 1900 1770 1630 1480 1300
060
Low
Watts 890 850 810 780 740 710 660 630 580
Cfm 2500 2410 2330 2260 2170 2080 1970 1860 1700
High
Watts 1000 960 910 870 830 790 750
Cfm 2480 2370 2250 2120 2000 1850 1690
Table 10 Dry-Coil Air Delivery* Horizontal Discharge (Deduct 10% for 208 V) Unit 50SX
UNIT
50SX
MOTOR
SPEED
AIR
DELIVERY
230 AND 460 VOLT HORIZONTAL DISCHARGE
External Static Pressure (in. wg)
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
024,
030
Low
Watts 280 275 265 255 250 245 240 ————
Cfm 820810755700660600560————
Med
Watts 365 360 350 345 340 330 320 310 300
Cfm 1025 1010 975 940 900 850 800 720 630
High
Watts 490 480 470 460 445 430 410 390 380
Cfm 1300 1255 1200 1150 1080 1005 915 790 620
036
Low
Watts 520 495 474 458 445 425 —————
Cfm 1375 1335 1290 1240 1200 1140 —————
Med
Watts 575 560 535 510 480 460 440 425
Cfm 1520 1490 1450 1400 1380 1300 1200 1080
High
Watts ————650614575540510480
Cfm ————1560 1500 1380 1280 1170 1060
042
Low
Watts 490 480 470 460 450 430 410 390
Cfm 1400 1380 1340 1300 1250 1200 1140 1070
Med
Watts 590 580 560 545 525 505 480 450 420
Cfm 1600 1560 1540 1470 1430 1360 1300 1220 1120
High
Watts —————700670640600560500
Cfm —————1780 1670 1600 1480 1340 1100
048†
Low
Watts 1050 1000 970 930 870 810 750 680 600
Cfm 1850 1830 1800 1785 1750 1700 1640 1500 1330
High
Watts 1050 1000 930 870 810 740 665
Cfm 2000 1940 1850 1750 1635 1500 1300
LEGEND AND NOTES FOR TABLES 9 AND 10
*Air delivery values are based on operating voltage of 230 v or
460 v, dry coil, without filter or electric heater. Deduct wet coil, filter,
and electric heater pressure drops to obtain external static pressure
available for ducting.
†Size 048 is 460 v.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than
350 cfmforeach 12,000Btuh ofratedcooling capacity.Evaporator-
coil frosting may occur at airflows below this point.
2. Dashes indicate portions of the table that are beyond the blower
motor capacity or are not recommended.
37