Carrier 50SS018-060 Air Conditioner User Manual


 
REQUIRED CLEARANCES TO COMBUSTIBLE MATERIAL — in. (mm)
Unit Top ....................................14(356)
Duct Side of Unit .................................2(51)
Side Opposite Ducts .............................14(356)
Bottom of Unit .....................................0
Vertical Discharge First 12 in. (305) of Supply Duct ...............1(25)
NECESSARY REQUIRED CLEARANCES — in. (mm)
Between Units, Control Box Side ......................42(1067)
Unit and Ungrounded Surfaces, Control Box Side ..............36(914)
Unit and Block or Concrete Walls and Other Grounded
Surfaces, Control Box Side .........................42(1067)
REQUIRED CLEARANCES FOR SERVICING — in. (mm)
Evaporator Coil Access Side .........................30(762)
Control Box Access Side ...........................30(762)
(Except for Necessary Requirements)
Unit Top ....................................36(914)
Side Opposite Ducts .............................30(762)
UNIT
50SS
CENTER OF GRAVITY (in./mm)
XYZ
048 21.9/555 19.6/498 13.4/341
060 22.2/565 19.8/503 13.4/340
LEGEND
CG Center of Gravity NEC National Electrical Code
COND Condenser REQ’D Required
MAT’L Material
NOTES:
1. Clearancesmust bemaintained to preventrecirculation ofair fromoutdoor-fan dis-
charge.
2. Dimensions in ( ) are in millimeters.
UNIT
50SS
ELECTRICAL
CHARACTERISTICS
UNIT WT CORNER WT (Lb/Kg)
Lb Kg A B C D
048 208/230-1-60, 208/230-3-60, 460-3-60 332 151 82/37 68/31 131/60 51/23
060 208/230-1-60, 208/230-3-60, 460-3-60 359 163 65/30 99/45 120/55 75/34
Fig. 4 Dimensions; Units 50SS048,060 Without Base Rail
4