Carrier 50SS018-060 Air Conditioner User Manual


 
REQUIRED CLEARANCES TO COMBUSTIBLE MATERIAL — in. (mm)
Unit Top ..................................14(356)
Duct Side of Unit ..............................2(51)
Side Opposite Ducts ...........................14(356)
Bottom of Unit ..................................0
Vertical Discharge First 12 in. (305) of Supply Duct ............1(25)
NECESSARY REQUIRED CLEARANCES — in. (mm)
Between Units, Control Box Side ....................42(1067)
Unit and Ungrounded Surfaces, Control Box Side ............36(914)
Unit and Block or Concrete Walls and Other Grounded
Surfaces, Control Box Side ......................42(1067)
REQUIRED CLEARANCES FOR SERVICING — in. (mm)
Evaporator Coil Access Side .......................30(762)
Control Box Access Side .........................30(762)
(Except for Necessary Requirements)
Unit Top ..................................36(914)
Side Opposite Ducts ...........................30(762)
UNIT
50SS
CENTER OF GRAVITY (in./mm)
XYZ
048 21.7/550 19.7/501 15.7/400
060 22.0/560 19.9/506 15.7/399
LEGEND
CG Center of Gravity NEC National Electrical Code
COND Condenser REQ’D Required
MAT’L Material
NOTES:
1. Clearancesmust bemaintained to preventrecirculation ofair fromoutdoor-fan dis-
charge.
2. Dimensions in ( ) are in millimeters.
UNIT
50SS
ELECTRICAL
CHARACTERISTICS
UNIT WT CORNER WT (Lb/Kg)
Lb Kg A B C D
048 208/230-1-60, 208/230-3-60, 460-3-60 352 160 87/40 73/33 136/62 56/25
060 208/230-1-60, 208/230-3-60, 460-3-60 379 172 70/32 104/47 125/57 80/36
Fig. 5 Dimensions; Units 50SS048,060 With Optional Base Rail
5