Table 13 -- 002 Sensor Standard Settings
ANALOG
OUTPUT
SETTING
1
2
3
4
5
6
7
8
EQUIPMENT
Interface with Standard
Building Control System
Economizer
Health & Safety
9 Parking/Air Intakes/
Loading Docks
LEGEND
ppm -- Parts Per Million
OUTPUT
Proportional
Proportional
Exponential
Proportional
Proportional
Exponential
Exponential
Proportional
Proportional
VENTILATION
RATE
(cfm/Pereon)
Any
Any
Any
15
20
15
20
0-10V
4-20 mA
2-10V
7-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
002
CONTROLRANGE
(ppm)
0-2000
0-2000
0-2000
0-1100
0- 900
0-1100
0- 900
0-9999
0-2000
OPTIONAL
RELAY SETPOINT
(ppm)
1000
1000
1100
1100
900
1100
900
5000
700
RELAY
HYSTERESIS
(ppm)
50
50
50
50
50
50
50
50O
50
Dehumidification of Fresh Air with DCV Control -- Infor-
mation flom ASHRAE indicates that the largest humidity load
on any zone is the flesh air introduced. For some applications,
a field-installed energy recovely unit can be added to reduce
the moisture content of file fiesh tfir being brought into the
building when the enthalpy is high. In most cases, the normal
heating and cooling processes are more than adequate to re-
move the humidity loads for most commerci_d applications.
If nonnal rooftop heating and cooling operation is not ade-
quate for the outdoor humidity level, an enel_y recovery unit
and/or a dehumidification option should be considered.
Step 14 -- Install Humidistat for Optional
MoistureMi$er TM Package-- MoistureMi$er dehu-
midification package operation can be controlled by field in-
stallation of a Canier-approved humidistat. To install the humi-
distat perform the following procedure:
1. Locate humidistat on a solid interior wall in the condi-
tioned space. Location should be a well ventilated area
to sense average humidity.
2. Route thermostat cable or equivalent single leads of col-
ored wire from Humidistat terminals through conduit in
unit to the low voltage connection on the 2-pole terminal
strip (TB3) as shown in Fig. 43 and Fig. 44. See Fig. 45
for operation_d diagram.
29