Carrier 48TJ016-028 Gas Heater User Manual


 
OPTIONAL NON-FUSED DISCONNECT -- On units with
the optiomfl non-fused disconnect, incoming power will be
wired into the disconnect switch. Refer to Fig. 16 for wiring
for 100 and 200 amp disconnect switches. Units with an
MOCP under 100 will use the 100 amp disconnect switch.
Units with an MOCP over 100 will use the 200 amp discon-
nect switch. Refer to the applicable disconnect wMng diagram.
To prevent breakage during shipping, the disconnect handle
and shaft are shipped and packaged inside the unit control box.
Install the disconnect handle before unit operation. To install
the handle and shaft, perform the following procedure:
1. Open the control box door and remove the handle and
shaft from shipping location.
2. Ix_osen the Allen bolt located on the disconnect switch.
The bolt is located on the square hole and is used to hold
the shaft in place. The shaft cannot be inserted until the
Allen bolt is moved.
3. Insert the disconnect shaft into the squae hole on the dis-
connect switch. The end of the shaft is specially cut and
the shaft can only be inserted in the correct orientation.
4. Tighten the Allen bolt to lock the shaft into position.
5. Close the control box dool:
6. Attach the handle to the external access door with the two
screws provided. When the handle is in the ON position,
the handle will be vertical. When the handle is in the OFF
position, the handle will be horizontal.
7. Turn the handle to the OFF position and close the dool:
The handle should fit over the end of the shaft when the
door is closed.
8. The handle must be in the OFF position to open the con-
trol box dool:
OPTIONAL CONVENIENCE OUTLET-- On units with
optiomfl convenience outlet, a 115-v GFI (ground fault inter-
rupt) convenience outlet receptacle is provided for field wiring.
Field wiring should be run through the 7Is-in. knockout pro-
vided in the basepan near the return air opening.
THERMOSTAT ASSEMBLY
I
_ Z Z
Lu q z cc o _, cc
cc m a_ o _ m m
Fig. 15 -- Field Control Thermostat Wiring
UNIT WIRING 6T3 4T2 2T1 LOAD
lO0 BLK, YEL. BLU.
AMP I
[ NON_:EPDOWDEIRsCONNE_T _-- _ _ OA: '
I ;_ ;__T2Ej
FIELD POWER SUPPLY 5L3 3L2 1L1 LINE
UNIT WIRING
200 BLK. YEL. BLU,
AMP 4--+--t--- '
[ NON FUSED DISCONNECT __i _i_ Lli E j
FIELD POWER SUPPLY
NOTE: The disconnect takes the place of TB-1 as shown on the unit wiring
diagram label and the component arrangement label.
Fig. 16- Optional Non-Fused Disconnect Wiring
12