TABLE 15 – 70 THROUGH 85 TON SUPPLY FAN DATA
TOTAL STATIC PRESSURE (Pascals of water column)
m3/hr 245 373 498 622 747
STD. AIR kW RPM kW RPM kW RPM kW RPM kW RPM
27184 4.2 397 5.5 467
30582 5.3 411 6.7 478 8.2 538 9.8 596 11.4 646
33980 6.4 425 7.9 488 9.5 547 11.2 599 13.0 648
37378 7.8 441 9.6 503 11.3 559 14.0 610 14.9 658
40776 9.3 457 11.2 517 14.0 570 16.0 620 16.9 667
44174 11.3 475 13.3 533 15.4 585 17.4 633 19.5 678
45873 12.1 483 14.4 540 16.5 592 18.6 639 2.8 684
47572 13.8 492 15.4 548 17.7 599 19.8 645 22.4 689
50970 15.5 511 18.2 565 2.5 615 22.8 660 25.1 703
54368 17.9 530 2.6 582 23.3 631 25.8 674 28.2 716
TABLE 15 – 70 THROUGH 85 TON SUPPLY FAN DATA (CONT’D)
TOTAL STATIC PRESSURE (Pascals of water column)
m3/hr 871 995 1120 1244 1369
STD. AIR kW RPM kW RPM kW RPM kW RPM kW RPM
27184
30582
33980 14.7 696
37378 16.8 704 18.6 745 2.9 791
40776 18.9 711 3.0 752 23.7 792 25.3 832 27.9 877
44174 21.6 721 23.8 762 26.0 801 28.3 840 3.8 879
45873 22.9 726 25.1 767 27.4 806 29.7 843 32.2 880
47572 24.3 731 26.5 772 28.8 810 31.2 847 33.7 881
50970 27.5 743.5 29.9 783 32.3 820 34.8 857 37.3 891
54368 3.8 756 33.3 794 35.8 830