York R-407C Air Conditioner User Manual


 
FORM 100.50-EG3 (802)
23
YORK INTERNATIONAL
TABLE 5 – COOLING PERFORMANCE DATA* – 65 TON MODEL (CONT’D)
40.5°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
46.1°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 210 165 209 143 208 127 207 111 206 95
23786 19 202 189 194 172 193 155 193 138 192 123 191 107
17 199 199 190 193 181 179 180 165 178 152 177 135
22 217 186 215 159 215 140 214 120 212 100
30582 19 210 213 202 194 200 174 200 154 198 135 197 115
17 214 214 204 207 196 199 187 185 185 169 184 149
22 222 199 219 169 219 148 218 126 216 104
35679 19 219 229 207 207 205 186 204 164 202 142 201 120
17 223 223 213 215 205 211 192 198 189 180 188 158
22 223 203 220 172 220 150 219 127 217 105
38228 19 222 231 209 211 206 189 205 166 204 144 202 121
17 225 225 215 218 207 213 193 202 190 183 189 161
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 201 161 200 139 199 123 198 107 197 91
23786 19 194 186 186 168 185 152 185 135 184 120 183 104
17 191 191 184 187 173 175 172 161 170 148 170 131
22 208 182 206 156 205 136 205 116 203 97
30582 19 202 207 192 188 192 170 191 150 190 131 189 111
17 206 206 195 197 188 192 182 184 177 165 176 145
22 212 195 211 166 209 144 209 122 207 100
35679 19 211 220 196 201 196 182 195 159 193 138 192 116
17 215 215 201 202 197 196 189 186 181 165 180 143
22 213 198 212 169 210 146 210 123 207 101
38228 19 214 223 197 205 197 185 196 162 194 140 193 118
17 217 217 202 199 200 183 191 162 182 142 181 120