TABLE 6 – COOLING PERFORMANCE DATA* – 70 TON MODEL (CONT’D)
40.5°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
46.1°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 221 185 220 159 218 139 218 119 216 100
27184 19 216 215 205 196 204 174 204 153 202 134 201 114
17 219 219 205 204 201 199 191 186 187 169 187 149
22 231 203 229 173 227 150 227 129 225 108
33980 19 232 242 218 216 213 191 212 167 211 145 209 123
17 236 235 224 226 216 222 204 204 196 184 195 161
22 234 215 232 182 230 157 230 133 228 111
37378 19 237 247 225 231 217 201 215 175 214 151 212 127
17 241 241 230 233 221 227 211 216 200 194 198 169
22 235 217 232 183 230 158 230 134 228 111
38228 19 238 248 226 233 217 203 216 176 214 152 213 128
17 242 242 232 234 221 228 212 218 201 195 199 170
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 215 184 213 157 212 138 211 118 209 99
27184 19 213 211 202 194 198 172 197 152 196 133 195 113
17 215 215 202 201 197 195 188 184 183 168 181 148
22 222 200 220 169 219 147 217 125 216 104
33980 19 224 234 209 212 205 187 204 163 202 141 201 119
17 228 228 215 217 209 215 196 200 189 181 187 158
22 225 211 223 178 221 153 220 129 218 107
37378 19 229 239 216 226 208 197 206 171 205 147 203 123
17 233 233 221 224 213 219 202 211 192 190 190 165
22 226 213 223 179 222 154 221 130 219 107
38228 19 230 240 217 228 209 199 207 172 205 148 204 124
17 234 234 222 225 214 220 204 213 193 192 191 167